AC1224 AS-Interface power supply PowerSupply 115/230VAC 4A
Brand: IFM Electronic
Code: AC1224
Application
Design | Integrated earth fault monitor |
---|
Electrical data
Frequency AC [Hz] | 47...63 |
---|---|
Nominal voltage AC [V] | 110 / 230 |
Input voltage range AC [V] | 85...132 / 184...264 |
Protection class | I |
Max. power-on delay time [ms] | 100 |
Output voltage AS-i [V] | 30.5 |
Output power (permanent) [W] | 122 |
Number of output circuits | 1 |
Output current AS-i [A] | 4 |
Max. residual ripple [mV] | 50 |
External input protection | B 6 A |
Derating [W/K] | 3 (60...70 °C) |
Integrated data decoupling | yes |
Outputs
Short-circuit protection | yes |
---|---|
Type of short-circuit protection | electronically protected |
Overload protection | yes |
Parallel connection of outputs possible | no |
Series connection of outputs possible | no |
Operating conditions
Ambient temperature [°C] | -10...70 | |
---|---|---|
Note on ambient temperature |
| |
Protection | IP 20 | |
Pollution degree | 2; (IEC 62103: conductive soiling not permitted) |
Tests / approvals
EMC |
| ||||||
---|---|---|---|---|---|---|---|
MTTF [years] | 139 |
AS-i classification
AS-i certificate | 42301 |
---|
Mechanical data
Weight [g] | 750 |
---|---|
Dimensions [mm] | 124 x 73 x 107 |
Materials | housing: steel sheet |
Displays / operating elements
Display |
|
---|
Remarks
Pack quantity | 1 pcs. |
---|
Electrical connection
Connection | terminals: ...4 mm² |
---|
Diagrams and graphs
block diagram | |
---|
output characteristics | |
---|
characteristic line for derating | |
---|
Check out any spare parts and components from the IFM Electronic catalog!
Do you want to order a AC1224 AS-Interface power supply PowerSupply 115/230VAC 4A with code: AC1224?
Leave your request on our website for immediate assistance!