AC402S AS-Interface PROFINET gateway with fail-safe PLC SmartPLC SafeLine 2ASi PN
Brand: IFM Electronic
Code: AC402S
- With integrated fieldbus interface and fail-safe PLC
- Reliable and fast data exchange with the sensor actuator level
- Colour display for indicating the status of all AS-i slaves
- User-friendly and simple configuration, set-up and diagnosis
- Quick-setup menu with intuitive operation
Application
Application | PROFINET gateway with safe preprocessing |
---|
Electrical data
Operating voltage [V] | 18...32 DC; (AUX) |
---|---|
Current consumption [mA] | < 750 |
Max. current consumption from AS-i [mA] | AS-i 1: 10 mA; AS-i 2: 10 mA |
Number of AS-i masters | 2 |
Electrical separation | yes |
Inputs
Input circuit of digital inputs | PNP; (type 2 according to IEC 61131-2) |
---|---|
Sensor supply of the inputs | to SELV/PELV |
Power supply [V] | 18...24 |
Outputs
Circuit | PNP |
---|---|
Voltage range DC [V] | 18...32; (to SELV/PELV) |
Max. current load per output [mA] | 500 |
Short-circuit proof | yes |
Electrically separated | yes |
Interfaces
Communication interface | Ethernet; OPC-UA |
---|
Protocol | EtherCAT |
---|---|
Usage type | data transmission; programming |
Transmission rate | 100 MBaud |
---|---|
Protocol | EtherNet/IP |
Usage type | programming |
Protocol | FSoE |
---|
Transmission rate | 10 MBaud; 100 MBaud |
---|---|
Connector type | RJ45 |
Protocol | Modbus TCP |
Usage type | programming |
Transmission rate | 100 MBaud | |
---|---|---|
Connector type | RJ45 | |
Protocol | PROFINET | |
Usage type | data transmission | |
Note on interfaces |
|
Transmission rate | 10 MBaud; 100 MBaud |
---|---|
Connector type | RJ45 |
Protocol | TCP/IP |
Usage type | programming |
Transmission rate | 10 MBaud; 100 MBaud |
---|---|
Connector type | RJ45 |
Protocol | UDP/IP |
Usage type | programming |
Operating conditions
Ambient temperature [°C] | 0...45 |
---|---|
Storage temperature [°C] | -20...70 |
Max. relative air humidity [%] | 95; (non condensing) |
Max. height above sea level [m] | 2000 |
Protection | IP 20 |
Safety classification
Complies with the requirements |
| ||
---|---|---|---|
Mission time TM [h] | 175200 | ||
Mission time TM (additional indication) |
| ||
PFH [1/h] | 1,21E-08 |
AS-i classification
AS-i version | 3.0 |
---|---|
AS-i profile | M4 |
AS-i certificate | 125301 |
Mechanical data
Weight [g] | 834 |
---|---|
Housing | housing for DIN rail mounting |
Materials | aluminium powder-coated; steel sheet galvanised; PC |
Displays / operating elements
Display |
|
---|
Accessories
Items supplied |
|
---|
Remarks
Pack quantity | 1 pcs. |
---|
Check out any spare parts and components from the IFM Electronic catalog!
Do you want to order a AC402S AS-Interface PROFINET gateway with fail-safe PLC SmartPLC SafeLine 2ASi PN with code: AC402S?
Leave your request on our website for immediate assistance!