DN4237 Switched-mode power supply 24 V DC PSU-3AC/24VDC-20A/IOL/IP67
Brand: IFM Electronic
Code: DN4237
- Protection of the wiring via configurable electronic circuit breakers
- Installation without control cabinet
- Additional diagnostics by measuring current, voltage and mains quality as well as counting operating hours
- Energy-efficient generation of extra-low voltage without power loss
- Output voltage, load currents, output circuit states and trigger cause are communicated via IO-Link
- Switching the output circuits on and off as well as resetting the circuit breakers is possible via IO-Link
Electrical data
Nominal voltage AC [V] | 400 / 480 |
---|---|
Nominal frequency AC [Hz] | 50...60 |
Input voltage range AC [V] | 323...552 |
Output voltage DC [V] | 24...28 |
Protection class | I |
Max. power-on delay time [ms] | 12 |
Output voltage tolerance [%] | 0.2 |
Max. output current at min. output voltage [A] | 20.8 |
Max. output current at max. output voltage [A] | 17.8 |
Output power (permanent) [W] | 500 |
Output power (peak) [W] | 1000 |
Power factor (nominal voltage 400 V AC / 50 Hz) | 0.94 |
Power factor (nominal voltage 480 V AC / 50 Hz) | 0.95 |
Number of output circuits | 4 |
Switch-on peak current (nominal voltage 400 V AC / 60 Hz) [A] | 2.1 |
Switch-on peak current (nominal voltage 480 V AC / 50 Hz) [A] | 2 |
Efficiency (nominal voltage 400 V AC / 60 Hz) [%] | 94.2 |
Efficiency (nominal voltage 480 V AC / 50 Hz) [%] | 94 |
Mains buffering time (nominal voltage 400 V AC / 60 Hz) [ms] | 24 |
Mains buffering time (nominal voltage 480 V AC / 50 Hz) [ms] | 24 |
Input current (nominal voltage 400 V AC / 60 Hz) [A] | 1.1 |
Input current (nominal voltage 480 V AC / 50 Hz) [A] | 0.9 |
Outputs
Load capacitance, total [mF] | 12.5 |
---|
Interfaces
Communication interface | IO-Link |
---|---|
Unterstützte Masterportklasse | A |
Transmission type | COM3 (230,4 kBaud) |
IO-Link revision | 1.1 |
SIO mode | yes |
Min. process cycle time [ms] | 2 |
Operating conditions
Ambient temperature [°C] | -25...70 |
---|---|
Storage temperature [°C] | -40...85 |
Max. relative air humidity [%] | 95; (relative humidity) |
Max. height above sea level [m] | 5000 |
Protection | IP 65; IP 67 |
Pollution degree | 3 |
Tests / approvals
EMC |
| ||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Continuous shock resistance |
| ||||||||||||||||||||||||||||||||||||||||||||||||||
Vibration resistance |
|
Mechanical data
Weight [g] | 1616.05 |
---|---|
Dimensions [mm] | 182 x 183 x 59 |
Materials | housing: aluminium alloy; housing cap: PC; screws: steel bronzed |
Remarks
Pack quantity | 1 pcs. |
---|
Electrical connection - IO-Link
Connector: 1 x M12; coding: A; Locking: brass |
Electrical connection - Output voltage
Connector: 2 x M12; coding: L; Locking: brass |
Electrical connection - power supply
Connector: 1 x 7/8"; Locking: brass |
Diagrams and graphs
block diagram | |
---|
output characteristics | |
---|
characteristic curve for degree of efficiency / power loss | |
---|
characteristic line for derating | |
---|
characteristic line for mains buffering time | |
---|
Check out any spare parts and components from the IFM Electronic catalog!
Do you want to order a DN4237 Switched-mode power supply 24 V DC PSU-3AC/24VDC-20A/IOL/IP67 with code: DN4237?
Leave your request on our website for immediate assistance!