Buy IFM Electronic SD5100

SD5100 - efector300-SDR14DGXFPKG/US-100

Code: SD5100
  • Precise measurement of flow, consumption and medium temperature
  • High accuracy, repeatability and measurement dynamics
  • For detecting compressed air in industrial use
  • With switching output, analogue output and pulse output
  • Clearly visible 4-digit LED display
Product characteristics
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Process connection threaded connection G 1/4 DN8
Ar
Measuring range [m³/h] 0.08...24.04
CO2
Measuring range [m³/h] 0.04...14.36
N2
Measuring range [m³/h] 0.04...15
Application
Application for industrial applications
Media Argon (Ar); carbon dioxide (CO2); nitrogen (N2)
Medium temperature [°C] 0...60
Pressure rating [bar] 16
Pressure rating [Mpa] 1.6
Electrical data
Operating voltage [V] 18...30 DC; (to SELV/PELV)
Current consumption [mA] < 100
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 1
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Outputs
Total number of outputs 2
Output signal switching signal; analogue signal; pulse signal; IO-Link; (configurable)
Electrical design PNP
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V] 2
Permanent current rating of switching output DC [mA] 250; (per output)
Number of analogue outputs 1
Analogue current output [mA] 4...20; (scalable)
Max. load [Ω] 500
Pulse output consumed quantity meter
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Low flow cut-off LFC [m³/h] < 0.26
Measuring dynamics 1:300
Ar
Measuring range [m³/h] 0.08...24.04
Display range [m³/h] 0...28.84
Resolution [m³/h] 0.02
Set point SP [m³/h] 0.22...24.04
Reset point rP [m³/h] 0.12...23.94
Analogue start point ASP [m³/h] 0...19.24
Analogue end point AEP [m³/h] 4.8...24.04
In steps of [m³/h] 0.02
CO2
Measuring range [m³/h] 0.04...14.36
Display range [m³/h] 0...17.24
Resolution [m³/h] 0.02
Set point SP [m³/h] 0.14...14.36
Reset point rP [m³/h] 0.08...14.3
Analogue start point ASP [m³/h] 0...11.48
Analogue end point AEP [m³/h] 2.88...14.36
In steps of [m³/h] 0.02
Volumetric flow quantity monitoring
Pulse value 0.001...1 000 000 m³
In steps of 0.001...1000 m³
Pulse length [s] 0,062...2
N2
Measuring range [m³/h] 0.04...15
Display range [m³/h] 0...18
Resolution [m³/h] 0.02
Set point SP [m³/h] 0.14...15
Reset point rP [m³/h] 0.08...14.94
Analogue start point ASP [m³/h] 0...12
Analogue end point AEP [m³/h] 3...15
In steps of [m³/h] 0.02
Temperature monitoring
Measuring range [°C] 0...60
Display range [°C] -12...72
Resolution [°C] 0.2
Set point SP [°C] 0.4...60
Reset point rP [°C] 0...59.8
Analogue start point [°C] 0...48
Analogue end point [°C] 12...60
In steps of [°C] 0.2
Accuracy / deviations
Flow monitoring
Repeatability [% of the measured value] ± 1,5
Accuracy (in the measuring range) ± (6 % MW + 0,6 % MEW); (conditions: installation to DIN ISO 2533)
Temperature monitoring
Accuracy [K] ± 2; (medium flow in the limit area of the flow measurement range)
Response times
Flow monitoring
Response time [s] 0.1; (dAP = 0)
Damping process value dAP in steps [s] 0 - 0,2 - 0,4 - 0,6 - 0,8 - 1
Software / programming
Parameter setting options Flow monitoring; quantity meter; Preset counter; hysteresis / window; normally open / normally closed; current/pulse output; display can be rotated and switched off; Display unit; medium selection
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
Profiles Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO mode yes
Required master port type A
Process data analogue 3
Process data binary 2
Min. process cycle time [ms] 4.1
Supported DeviceIDs
Type of operation DeviceID
Default 263
Operating conditions
Ambient temperature [°C] 0...60
Storage temperature [°C] -20...85
Max. relative air humidity [%] 90
Protection IP 65
Tests / approvals
EMC
EN 61000-4-2 ESD 4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated 10 V/m
EN 61000-4-4 Burst 2 kV
EN 61000-4-6 HF conducted 10 V
CPA approval
model number 003TG
accuracy class -
maximum allowable error ± 7 % FS
Q (min) 0,04 m³/h (N2)
0,04 m³/h (CO2)
0,08 m³/h (Ar)
Q (t) -
Q (max) 15 m³/h (N2)
14,36 m³/h (CO2)
24,04 m³/h (Ar)
Vibration resistance
DIN IEC 68-2-6 5 g (55...2000 Hz)
MTTF [years] 227
Pressure Equipment Directive Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight [g] 981
Materials PBT-GF20; PC; PC; stainless steel (1.4301 / 304); FKM
Materials (wetted parts) stainless steel (1.4301 / 304); ceramics glass passivated; PEEK; polyester; FKM; aluminium anodised
Process connection threaded connection G 1/4 DN8
Displays / operating elements
Display
Display unit 4 x LED, green (Nl/min, Nm³/h, Nm³, °C)
function display 1 x LED, yellow
switching status 2 x LED, yellow
measured values alphanumeric display, 4-digit
programming alphanumeric display, 4-digit
Display unit Nl/min; Nm³/h; Nm³; °C
Remarks
Remarks
MW = measured value
MEW = Final value of the measuring range
Measuring, display and setting ranges refer to the standard volume flow according to DIN ISO 2533.
For information about installation and operation please see the operating instructions.
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; coding: A

Check out any spare parts and components from the IFM Electronic catalog!


Do you want to order a SD5100 - efector300-SDR14DGXFPKG/US-100 with code: SD5100?


Leave your request on our website for immediate assistance!

OUR TOP BRANDS