SV7050 - efector300-SVM11XXXD0KG/US-100
Brand: IFM Electronic
Code: SV7050
- Reliable detection of flow and medium temperature
- Precise linearized analogue output
- Suitable for water and water-based media
- For installation in pipes
- High precision of flow and temperature monitoring
Product characteristics
Number of inputs and outputs | Number of analogue outputs: 1 | ||
---|---|---|---|
Measuring range |
| ||
Process connection | threaded connection G 1 DN20 |
Application
Special feature | Gold-plated contacts | |
---|---|---|
Measuring element | 1 x Pt 1000; (to DIN EN 60751, class B) | |
Application | for industrial applications | |
Installation | connection to pipe by means of an adapter | |
Media | water; glycol solutions; coolants | |
Medium temperature [°C] | -40...100 | |
Min. bursting pressure [bar] | 25 | |
Min. bursting pressure [MPa] | 2.5 | |
Pressure rating [bar] | 12 | |
Pressure rating [Mpa] | 1.2 | |
Note on pressure rating |
|
Electrical data
Operating voltage [V] | 8...33 DC |
---|---|
Min. insulation resistance [MΩ] | 100; (500 V DC) |
Protection class | III |
Power-on delay time [s] | < 2 |
Inputs / outputs
Number of inputs and outputs | Number of analogue outputs: 1 |
---|
Outputs
Total number of outputs | 1 |
---|---|
Output signal | analogue signal |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4...20; (water: Q [l/min] = 5,313 x (I - 4 mA); water-glycol: Q [l/min] = 5,313 x (I - 4 mA) - Qo see Figure 2) |
Max. load [Ω] | < (Ub - 8 V) / 20 mA; Ub = 24 V: 800 |
Measuring/setting range
Measuring range |
|
---|
Internal heating temperature probe | 1 K/mW |
---|---|
Measuring range [°C] | -40...100 |
Accuracy / deviations
Accuracy (in the measuring range) | Q < 50 % MEW: < 1 % MEW / Q > 50 % MEW: < 2 % MW; (water) |
---|---|
Repeatability | 0,2; (% of the final value) |
Accuracy [K] | ± 0,3 ± 0,005 x T |
---|
Response times
Response time [s] | 0.5 |
---|
Operating conditions
Ambient temperature [°C] | -15...85 |
---|---|
Storage temperature [°C] | -30...85 |
Protection | IP 65 |
Cavitation | P(absolute) discharge / P(difference) > 5.5 to avoid cavitation |
Tests / approvals
EMC |
| ||||
---|---|---|---|---|---|
Shock resistance |
| ||||
Vibration resistance |
| ||||
MTTF [years] | 380 | ||||
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical data
Weight [g] | 105.5 |
---|---|
Materials | PA 6T |
Materials (wetted parts) | ETFE; PA 6T; FKM |
Tightening torque [Nm] | 12 |
Process connection | threaded connection G 1 DN20 |
Remarks
Remarks |
| ||
---|---|---|---|
Pack quantity | 1 pcs. |
Electrical connection
Connection | Connector: 1 x M12; coding: A; Contacts: gold-plated |
---|
Diagrams and graphs
Pressure loss |
|
---|
min. life 10 years referred to flow and high medium temperatures | |
---|
determination of the kinematic viscosity (v) of glycol-water mixtures depending on the temperature | |
---|
determination of the compensation value Qo for glycol-water mixtures |
|
---|
response threshold Q(min) depending on the kinematic viscosity | |
---|
pressure rating (bar) | |
---|
Check out any spare parts and components from the IFM Electronic catalog!