Datasheet excerpt: Technical data of  U-P6-B6

Product Description
Base for PROFIBUS DP
Indicators/operating means
DIP switchSetting the station address
bus connection
ON = active  OFF = non-active
Electrical specifications
Rated operating voltage20 ... 30 V DC , ripple 10 %SS , PELV
Power consumptionmax. 5 W with read/write head IPT*-FP
Galvanic isolation
Operating voltage/interfacefunctional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Interface
Physical RS-485
ProtocolPROFIBUS DP acc. to EN 50170
Transfer rate9.6; 19.2; 93.75; 187.5; 500; 1500 kBit/s
3; 6; 12 Mbit/s self-synchronizing
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Degree of protectionIP67 according to EN 60529 with IPT*-FP
Connectionscrew terminals
Interface cable2 x 0.64 mm2, double screened, acc. to PROFIBUS standard EN 50170
Supplyup to 3 x 1.5 mm2
Material
Housingaluminum, black anodized

Classifications

SystemClasscode
ECLASS 13.027280492
ECLASS 12.027280490
ECLASS 11.027280490
ECLASS 10.0.127280490
ECLASS 9.027280490
ECLASS 8.027280490
ECLASS 5.127279212
ETIM 9.0EC002997
ETIM 8.0EC002997
ETIM 7.0EC002997
ETIM 6.0EC002997
ETIM 5.0EC003015
UNSPSC 12.131162301