Buy Pepperl+Fuchs UC400-F77-EP-IO-V31

Ultrasonic sensor UC400-F77-EP-IO-V31

Code: UC400-F77-EP-IO-V31

Single head system, IO-Link interface for service and process data, Programmable via DTM with PACTWARE, Continuous distance value via IO-Link process data, Series: -F77, Operating voltage: 10 ... 30 V DC , ripple 10 %SS, Interface type: IO-Link (via C/Q = Pin 4), Output type: 1 push-pull (4 in 1) output, short-circuit protected, reverse polarity protected, UL approval: cULus Listed, Class 2 Power Source, CCC approval: CCC approval / marking not required for products rated ≤36 V

Datasheet excerpt: Technical data of  UC400-F77-EP-IO-V31

Product Description
Single head system
General specifications
Sensing range30 ... 400 mm
Adjustment range40 ... 400 mm
Dead band0 ... 30 mm
Standard target plate20 mm x 20 mm
Transducer frequencyapprox. 310 kHz
Response delayminimum : 10 ms
factory setting: 37 ms
Sensor cycle time≥ 10 ms (factory setting) ;
programmable to 60 s
Memory
Non-volatile memoryEEPROM
Write cycles300000
Indicators/operating means
LED greensolid: power on
flashing: standby mode or IO-Link communication
LED yellowsolid: object in evaluation range
flashing: switch point programming, object detected
LED redsolid: error
flashing: switch point programming, object not detected
Electrical specifications
Operating voltage10 ... 30 V DC , ripple 10 %SS
No-load supply current≤ 40 mA
Power consumption≤ 400 mW
Time delay before availability≤ 300 ms
Interface
Interface typeIO-Link (via C/Q = Pin 4)
IO-Link revision1.1
Device profileSmart Sensor
Device ID0x300301 (3146497)
Transfer rateCOM2 (38.4 kBit/s)
Min. cycle time2.3 ms
Process data width16 bit
SIO mode supportyes
Compatible master port typeA
Input/Output
Input/output type1 synchronization connection, bidirectional
0 Level0 ... 1 V
1 Level2.5 V ... UB
Input impedance> 22 kΩ
Output rated operating currentcurrent source < 2.5 mA
Pulse length≥ 1 ms with external control, low active
Synchronization frequency
Common mode operation≤ 109 Hz
Multiplex operation≤ 109 Hz / n , n = number of sensors , n ≤ 10
Output
Output type1 push-pull (4 in 1) output, short-circuit protected, reverse polarity protected
Rated operating current100 mA , short-circuit/overload protected
Voltage drop≤ 2.5 V
Repeat accuracy≤ ± 0.1 % of full-scale value
Switching frequencyfactory setting: 16 Hz programmable max. 35 Hz
Range hysteresis1 % of the adjusted operating range (default settings), programmable , min. 1 mm
Temperature influence≤ ± 0.75 % of the end value (with temperature compensation) from 10 minutes after switching on the sensor ; 0.17 %/K (without temperature compensation)
Compliance with standards and directives
Standard conformity
StandardsEN IEC 60947-5-2:2020
IEC 60947-5-2:2019
IEC 61131-9:2013
Approvals and certificates
UL approvalcULus Listed, Class 2 Power Source
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection typeConnector plug M8 x 1 , 4-pin
Degree of protectionIP67
Material
HousingPolycarbonate
Transducerepoxy resin/hollow glass sphere mixture; polyurethane foam
Installation positionany position
Mass9 g
Tightening torque, fastening screwsmax. 0.2 Nm
Factory settings
Outputnear switch point: 40 mm
far switch point: 400 mm
Output mode: Window mode
Output logic: normally open
Beam widthwide

Classifications

SystemClasscode
ECLASS 13.027272803
ECLASS 12.027272803
ECLASS 11.027272803
ECLASS 10.0.127272803
ECLASS 9.027272803
ECLASS 8.027272803
ECLASS 5.127272803
ETIM 9.0EC001849
ETIM 8.0EC001849
ETIM 7.0EC001849
ETIM 6.0EC001849
ETIM 5.0EC001849
UNSPSC 12.141111960

Check out any spare parts and components from the Pepperl+Fuchs catalog!


Do you want to order a Ultrasonic sensor UC400-F77-EP-IO-V31 with code: UC400-F77-EP-IO-V31?


Leave your request on our website for immediate assistance!