AS-Interface safety module VAA-2E-KE1-S
Brand: Pepperl+Fuchs
Code: VAA-2E-KE1-S
KE1 safety module for the control cabinet, 2 Safety-related inputs
Datasheet excerpt: Technical data of VAA-2E-KE1-S
Product Description |
---|
KE1 safety module for the control cabinet, 2 Safety-related inputs |
General specifications | ||
---|---|---|
Node type | Safety node | |
AS-Interface specification | V2.11 | |
Required gateway specification | ≥ V2.0 | |
Profile | S-0.B | |
IO code | 0 | |
ID code | B | |
ID1 code | F | |
ID2 code | 0 | |
UL File Number | E87056 | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 / PL e | |
MTTFd | 200 a | |
Indicators/operating means | ||
LED FAULT | error display; LED red red: communication error or address is 0 | |
LED PWR | AS-Interface voltage; LED green | |
LED IN | switching state (input); 2 LED yellow | |
Electrical specifications | ||
Rated operating voltage | 26.5 ... 31.6 V PELV from AS-Interface | |
Rated operating current | ≤ 70 mA | |
Protection class | III | |
Input | ||
Number/Type | 2 safety-related inputs for mechanical contacts, cross-circuit monitored: 2 single-channel contacts: up to category 2 / PL c according to EN ISO 13849-1 or 1 two-channel contact: up to category 4 / PL e according to EN ISO 13849-1 Cable length must not exceed 300 m per input. | |
Supply | from AS-Interface | |
Voltage | 20 ... 30 V DC pulsed | |
Current loading capacity | input current limited ≤ 15 mA, overload and short-circuit resistant | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013+A1:2019 | |
Standard conformity | ||
Insulation coordination | EN 50178:1998 | |
Electromagnetic compatibility | EN 61000-6-2, EN 61000-4-5 1 kV asymmetric, criterion B, EN 61000-6-4 | |
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013+A1:2019 | |
Electrical safety | EN 50178:1998 IEC 60204-1:2007 | |
Emitted interference | EN 61000-6-4:2001 | |
AS-Interface | EN 62026-2:2013 | |
Functional safety | Category 4 / PL e to EN ISO 13849-1:2015 SIL 3 according to IEC 62061:2015 and IEC 61508 Part 1-7:2010 | |
Standards | NFPA 79:2002 | |
Ambient conditions | ||
Ambient temperature | -25 ... 50 °C (-13 ... 122 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Shock and impact resistance | 10 g, 16 ms in 6 spatial directions 1000 shocks | |
Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | removable terminals, terminal connection ≤ 2.5 mm2 | |
Material | ||
Housing | PA 66-FR | |
Mass | 80 g | |
Mounting | DIN mounting rail |
Classifications
System | Classcode |
---|---|
ECLASS 13.0 | 27272603 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
Check out any spare parts and components from the Pepperl+Fuchs catalog!
Do you want to order a AS-Interface safety module VAA-2E-KE1-S with code: VAA-2E-KE1-S?
Leave your request on our website for immediate assistance!