Buy Pepperl+Fuchs VAA-2E1A-F85A/CB10-S-V1

AS-Interface EMERGENCY STOP button VAA-2E1A-F85A/CB10-S-V1

Code: VAA-2E1A-F85A/CB10-S-V1

AS-Interface EMERGENCY STOP button

Datasheet excerpt: Technical data of  VAA-2E1A-F85A/CB10-S-V1

Product Description
AS-Interface EMERGENCY STOP button
General specifications
Node typeSafety node
AS-Interface specificationV3.0
Required gateway specification≥ V2.1
ProfileS-7.B
IO code7
ID codeB
ID1 codeF
ID2 code0
UL File NumberE305142
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
CategoryCat. 4
Reaction time< 300 µs
MTTFdno significant contribution to MTTFd of the overall system
PFHdno significant contribution to PFH of the overall system
B10d250000 cycles
Design lifetime20 a
Indicators/operating means
Button
EMERGENCY STOPilluminated
Electrical specifications
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 80 mA
Protection classIII
Surge protectionUe: Over voltage category III, safe isolated power supplies (PELV)
Rated insulation voltage32 V
Pulse withstand voltage0.8 kV
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUIEC 62026-2:2013 EN 61000-6-2:2005 EN 61000-6-4:2007 A1:2011-02 EN 61326-1:2013
Machinery Directive
Directive 2006/42/ECEN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 EN 60947-5-5:1997+A1:2005+A11:2013+A2:2017
Standard conformity
Degree of protectionEN 60529:2000
Electrical safetyIEC 61140:2009
Emitted interferenceEN 61000-6-4:2007 A1:2011-02
AS-InterfaceEN 62026-2:2013
Noise immunityIEC 62026-2:2013 EN 61326-3-1:2017 EN 61000-6-2:2005
Functional safetyEN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 EN 60947-5-5:1997+A1:2005+A11:2013+A2:2017
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 5000 m above MSL
Shock and impact resistance30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm 10 ... 57 Hz , 5 g 57 ... 2000 Hz, 10 cycles
Pollution degree2
Mechanical specifications
Operating forcePush: 32 N
Pull: 21 N
Turn: 0.27 Nm
Minimum for positive opening operation: 60 Nm
Operating distancefor positive opening operation: min. 4 mm
maximal: 4.5 mm
Degree of protectionIP65
ConnectionM12 round connector
Material
HousingPolycarbonate
Mass225 g
Life span> 250,000 switching operations

Classifications

SystemClasscode
ECLASS 13.027371244
ECLASS 12.027371244
ECLASS 11.027371244
ECLASS 10.0.127371244
ECLASS 9.027371244
ECLASS 8.027371244
ECLASS 5.127371228
ETIM 9.0EC002034
ETIM 8.0EC002034
ETIM 7.0EC002034
ETIM 6.0EC002034
ETIM 5.0EC002034
UNSPSC 12.139121533

Check out any spare parts and components from the Pepperl+Fuchs catalog!