General specifications
Node typeSafety-Slave
AS-Interface specificationV3.0
Required gateway specification≥ V2.1
UL File NumberE223772
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
CategoryCat. 4
Mission Time (TM)20 a
PFHd2.83 E-9
PFD8 E-7
Indicators/operating means
LED FAULTFault indication: red LED
Red: communication error or address is 0
Red flashing: peripheral fault
LED AS-iAS-Interface voltage; LED green
LED AUXauxiliary voltage UAUX ; LED green
LED INswitching state (input); 2 LED yellow
LED OUTSwitching state (output); 2 LED yellow
Electrical specifications
Auxiliary voltage (output)24 V (20 VDC… 30 VDC)
Rated operating voltage22 ... 31.6 V
Rated operating current≤ 70 mA
Protection classIII
Current consumptionmax. 35 mA (AS-Interface)
max. 4 A (AUX)
Surge protectionUAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
Input
Number/Type2 inputs for a 2-channel active optoelectronic protective devices (AOPD) for safeguarding positions and areas of danger up to PL e in accordance with EN / ISO 13849-1
Supplyfrom AUX
Voltage20 ... 30 V DC pulsed
Current loading capacity1800 mA for power supply of external sensors from AUX
Switching pointVin> 11 V for high level, input current ≥ 2.5 mA at 15 V
Output
Number/Type2 conventional electronic outputs, short-circuit proof
Supplyfrom AUX
Current1 A per output
note derating
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61326-3-1:2008
Standard conformity
Electromagnetic compatibilityEN 61000-6-2:2005, EN 61000-6-3:2007/A1:2011 EN 61131-2:2007
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
AS-InterfaceEN 62026-2:2013
Functional safetyEN ISO 13849-1:2008 up to PL e EN 62061:2005/A1:2013 up to SIL 3
Programming instructions
ProfileS-7.B.1.
IO code7
ID codeB
ID1 codeF
ID2 code1
Data bits (function via AS-Interface)InputOutput
D0 dyn. safety code 1 OUT 1
D1 dyn. safety code 1 OUT 2
D2 dyn. safety code 2 -
D3 dyn. safety code 2 -
Parameter bits (programmable via AS-i)function
P0Communication monitoring
P0 = 0 monitoring = off, the outputs maintain the status if communication fails
P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
P1not used
P2not used
P3not used
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F) , no moisture condensation
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Altitude≤ 2000 m above MSL
Shock and impact resistance≤ 15 g at T ≤ 11 ms, 10 ... 55 Hz, 0,5 mm amplitude
Mechanical specifications
Degree of protectionIP20
Connectionremovable terminals, terminal connection 0.2 ... 2.5 mm2
Material
HousingPA 66-FR
Mass60 g
MountingDIN mounting rail
Tightening torque of clamping screws0.5 Nm ... 0.6 Nm

Classifications

SystemClasscode
ECLASS 13.027272603
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Check out any spare parts and components from the Pepperl+Fuchs catalog!


Do you want to order a AS-Interface safety module VAA-2E2A-KE1-SE with code: VAA-2E2A-KE1-SE?


Leave your request on our website for immediate assistance!

OUR TOP BRANDS