KE1-Safety module for the control cabinet
2 safety-related inputs and
2 conventional electronic outputs

Datasheet excerpt: Technical data of  VAA-2E2A-KE1P-S/E2

Product Description
KE1-Safety module for the control cabinet
2 safety-related inputs and
2 conventional electronic outputs
General specifications
Node typeSafety-Slave
AS-Interface specificationV2.1
Required gateway specification≥ V2.1
UL File NumberE223772
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
MTTFd200 a
PFHd0
PFD0
Indicators/operating means
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: Output supply overload
LED PWRAS-Interface voltage; LED green
LED AUXext. auxiliary voltage UAUX ; LED green
LED INswitching state (input); 2 LED yellow
LED OUTSwitching state (output); 2 LED yellow
Electrical specifications
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 70 mA
Protection classIII
Surge protectionUAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
Input
Number/Type2 safety-related inputs for mechanical contacts, crossed-circuit monitored:
2 single-channel contacts: up to category 2/PL c to ISO 13849-1 or
1 2-channel contact: up to category 4/PL e to ISO 13849-1
Cable length must not exceed 300 m per input.
Supplyfrom AS-Interface
Voltage20 ... 30 V DC pulsed
Current loading capacityinput current limited ≤ 15 mA,
overload and short-circuit resistant
Output
Number/Type2 conventional electronic outputs, PNP
Supplyfrom external auxiliary voltage UAUX
Voltage≥ (UAUX - 0.5 V)
Current0.5 A per output
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61496-1:2004
Standard conformity
Insulation coordinationEN 50178:1998
Electromagnetic compatibilityEN 61000-6-2:2005, EN 61000-4-5:2005 1 kV asymmetric, criterion B, EN 61000-6-4:2007
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
Electrical safetyEN 50178:1998 IEC 60204-1:2007
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Functional safetyEN ISO 13849-1:2015 up to PL e, IEC 61508:2010 and IEC 62061:2005/A2:2015 up to SIL 3
StandardsNFPA 79:2002
Programming instructions
ProfileS-7.B
IO code7
ID codeB
ID1 codeF
ID2 code0
Data bits (function via AS-Interface)InputOutput
D0 dyn. safety code 1 OUT 1
D1 dyn. safety code 1 OUT 2
D2 dyn. safety code 2 -
D3 dyn. safety code 2 -
Parameter bits (programmable via AS-i)function
P0Logic operation:
P0 = 1 (default settings): The outputs are controlled via AS-Interface.
P0 = 0: The outputs are controlled via AS-Interface or the inputs. The corresponding output is activated on opening the contacts of an input.
P1not used
P2not used
P3not used
Ambient conditions
Ambient temperature-25 ... 50 °C (-13 ... 122 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Shock and impact resistance10 g, 16 ms in 6 spatial directions 1000 shocks
Vibration resistance0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree2
Mechanical specifications
Degree of protectionIP20
Connectionremovable spring terminals
Conductor cross-section 0,25 ... 2,5 mm2
Material
HousingPA 66-FR
Mass80 g
MountingDIN mounting rail
Tightening torque of clamping screws0.5 Nm ... 0.6 Nm

Classifications

SystemClasscode
ECLASS 13.027272603
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Check out any spare parts and components from the Pepperl+Fuchs catalog!


Do you want to order a AS-Interface safety module VAA-2E2A-KE1P-S/E2 with code: VAA-2E2A-KE1P-S/E2?


Leave your request on our website for immediate assistance!

OUR TOP BRANDS