AS-Interface sensor/actuator module VAA-4E4A-KE5-ZEJQ/E2L
Brand: Pepperl+Fuchs
Code: VAA-4E4A-KE5-ZEJQ/E2L
Cabinet module
4 inputs and 4 outputs
Datasheet excerpt: Technical data of VAA-4E4A-KE5-ZEJQ/E2L
Product Description |
---|
Cabinet module 4 inputs and 4 outputs |
General specifications | ||
---|---|---|
Node type | Standard node | |
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V2.0 | |
UL File Number | E223772 | |
MTBF | 141 a | |
Indicators/operating means | ||
LED FAULT | Error display; red LED red: communication error, i.e. address is 0 red flashing: overload internal input supply, i.e. overload or lead interruption outputs | |
LED INT | Internal input supply active; LED green | |
LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 | |
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage | |
LED IN | switching state (input); 4 LED yellow | |
LED OUT | switching state (output); 4 LED yellow/red yellow: output active red: output overload or lead interruption | |
Electrical specifications | ||
Auxiliary voltage (input) | 12 ... 30 V DC PELV | |
Auxiliary voltage (output) | 20 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 35 mA (without sensors) / max. 190 mA | |
Protection class | III | |
Surge protection | UEXT, UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) Overvoltage category of the power supplies (primary): III | |
Rated insulation voltage | 92 V | |
Pulse withstand voltage | 0.8 kV | |
Input | ||
Number/Type | 4 inputs for 3-wire sensors (PNP), DC | |
Supply | from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT) | |
Voltage | 21 ... 31 V DC (INT) | |
Current loading capacity | ≤ 150 mA, overload- and short-circuit protected (INT) | |
Input current | ≤ 5.6 mA (max.) | |
Switching point | according to DIN EN 61131-2 (type 1) | |
0 (unattenuated) | ≤ 0.5 mA | |
1 (attenuated) | ≥ 2 mA | |
Signal delay | < 1 ms (input/AS-Interface) | |
Output | ||
Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof | |
Supply | from external auxiliary voltage UAUX | |
Voltage | ≥ (UAUX - 0.5 V) | |
Current | 2 A Per output, total 4 A (TB ≤ 60 °C) 1 A Per output, total 4 A (TB ≤ 70 °C) | |
Usage category | DC-13 | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 | |
Machinery Directive | ||
Directive 2006/42/EC | EN ISO 13849-1:2008 , EN ISO 13849-2:2012 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Electrical safety | IEC 61140:2009 | |
Input | EN 61131-2:2004 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026:2013 | |
Functional safety | EN ISO 13849-1:2008 EN ISO 13849-2:2012 | |
Programming instructions | ||
Profile | S-7.0 | |
IO code | 7 | |
ID code | 0 | |
ID1 code | F | |
ID2 code | E | |
Data bits (function via AS-Interface) | ||
D0 | ||
D1 | ||
D2 | ||
D3 | ||
Parameter bits (programmable via AS-i) | function | |
P0 | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) | |
P1 | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) | |
P2 | Lead breakage outputs P2 = 0 lead breakage on P2 = 1 lead breakage off (default settings) | |
P3 | not used | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
Pollution degree | 2 | |
Mechanical specifications | ||
Degree of protection | IP20 For safety applications: Installation in an enclosure with a minimum protection class of IP54 required | |
Connection | Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 | |
Material | ||
Housing | PA 66-FR | |
Mass | 110 g | |
Mounting | DIN mounting rail |
Classifications
System | Classcode |
---|---|
ECLASS 13.0 | 27242604 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
Check out any spare parts and components from the Pepperl+Fuchs catalog!
Do you want to order a AS-Interface sensor/actuator module VAA-4E4A-KE5-ZEJQ/E2L with code: VAA-4E4A-KE5-ZEJQ/E2L?
Leave your request on our website for immediate assistance!