Datasheet excerpt: Technical data of VAR-KE3-TERM
Product Description |
---|
AS-Interface advanced repeater with terminator |
General specifications | ||
---|---|---|
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V2.0 | |
UL File Number | E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source | |
Functional safety related parameters | ||
MTTFd | 155 a | |
Indicators/operating means | ||
Switch | TERM ON/OFF switches the segment A terminator on/off | |
LED FAULT SEG A | Segment A error display; red LED red: communication error | |
LED FAULT SEG B | Segment B error display; red LED red: communication error | |
LED PWR SEG A | AS interface voltage segment A; green LED | |
LED PWR SEG B | AS-Interface voltage segment B; green LED | |
LED TERM | Segment A bus terminator switched on | |
LED U>26V | Segment A voltage > 26 V | |
LED U>18,5V | Segment A voltage > 18.5 V | |
Electrical specifications | ||
Insulation voltage | ≥ 500 V | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | 60 mA (per strand element), 120 mA (total) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 EN 61000-6-3:2001 IEC 62026-2:2008 | |
Approvals and certificates | ||
UL approval | An isolated source with a secondary open circuit voltage of ≤ 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device. | |
Ambient conditions | ||
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
Storage temperature | -25 ... 75 °C (-13 ... 167 °F) | |
Mechanical specifications | ||
Housing width | 22.5 mm | |
Housing height | 99 mm | |
Housing depth | 114 mm | |
Degree of protection | IP20 according to EN 60529 | |
Connection | removable terminals, terminal connection ≤ 2.5 mm2 | |
Material | ||
Housing | PA 66-FR | |
Mounting | DIN mounting rail |
Classifications
System | Classcode |
---|---|
ECLASS 13.0 | 27040301 |
ECLASS 12.0 | 27040301 |
ECLASS 11.0 | 27040301 |
ECLASS 10.0.1 | 27040301 |
ECLASS 9.0 | 27040301 |
ECLASS 8.0 | 27040301 |
ECLASS 5.1 | 27040301 |
ETIM 9.0 | EC001449 |
ETIM 8.0 | EC001449 |
ETIM 7.0 | EC001449 |
ETIM 6.0 | EC001449 |
ETIM 5.0 | EC002540 |
UNSPSC 12.1 | 39121535 |
Check out any spare parts and components from the Pepperl+Fuchs catalog!
Do you want to order a AS-Interface repeater VAR-KE3-TERM with code: VAR-KE3-TERM?
Leave your request on our website for immediate assistance!