AS-Interface analog module VBA-2E-G4-U
Brand: Pepperl+Fuchs
Code: VBA-2E-G4-U
G4 module IP65
2 analog inputs (voltage)
Datasheet excerpt: Technical data of VBA-2E-G4-U
Product Description |
---|
G4 module IP65 2 analog inputs (voltage) |
General specifications | ||
---|---|---|
Node type | Standard node | |
AS-Interface specification | V2.1 | |
Required gateway specification | ≥ V2.1 | |
UL File Number | E223772 | |
Functional safety related parameters | ||
MTTFd | 160 a at 30 °C | |
Indicators/operating means | ||
LED FAULT | error display; LED red red: communication error red flashing: peripheral error | |
LED PWR | AS-Interface voltage; LED green | |
LED ANALOG | status input signal; LED green off: not connected (peripheral error) green: 0 V ≤ U ≤ 11.5 V green flashing: U > 11.5 V (peripheral error) | |
LED AUX | ext. auxiliary voltage UAUX ; LED green | |
Electrical specifications | ||
Auxiliary voltage (output) | 24 V DC ± 15 % PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 80 mA | |
Protection class | III | |
Input | ||
Number/Type | 2 analog inputs (voltage), 0 ... 10 V | |
Supply | from AS-Interface or from external auxiliary voltage as required UAUX | |
Current loading capacity | ≤ 200 mA from AS-Interface ≤ 500 mA from external auxiliary voltage UAUX | |
Input resistance | 100 kΩ | |
Resolution | 16 Bit / 1 mV | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
AS-Interface | EN 62026-2:2013 | |
Programming instructions | ||
Profile | S-7.3.D | |
IO code | 7 | |
ID code | 3 | |
ID2 code | D | |
Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. | |
Parameter bits (programmable via AS-i) | function | |
P0 | mains power frequency filter P0=1, 50 Hz filter active P0=0, 60 Hz filter active | |
P1 | projecting of the 2nd channel P1=1, channel 2 is projected P1=0, channel 2 is not projected | |
P2 | Message of peripheral error P2=1, peripheral error is reported P2=0, peripheral error is not reported | |
P3 | not used | |
Ambient conditions | ||
Ambient temperature | 0 ... 70 °C (32 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP65 | |
Connection | cable piercing method or terminal compartment yellow flat cable/black flat cable or standard round cable inputs/outputs: 2 x M16 x 1.5 cable glands and cage tension spring terminals, 1 x M12 x 1.5 cable gland (not used) | |
Material | ||
Housing | PA 6 GF30 | |
Mass | 350 g | |
Mounting | DIN mounting rail |
Classifications
System | Classcode |
---|---|
ECLASS 13.0 | 27242601 |
ECLASS 12.0 | 27242601 |
ECLASS 11.0 | 27242601 |
ECLASS 10.0.1 | 27242601 |
ECLASS 9.0 | 27242601 |
ECLASS 8.0 | 27242601 |
ECLASS 5.1 | 27242601 |
ETIM 9.0 | EC001596 |
ETIM 8.0 | EC001596 |
ETIM 7.0 | EC001596 |
ETIM 6.0 | EC001596 |
ETIM 5.0 | EC001596 |
UNSPSC 12.1 | 39121535 |
Check out any spare parts and components from the Pepperl+Fuchs catalog!