Buy Pepperl+Fuchs VBA-2E-KE2-I/U-V3.0

AS-Interface analog module VBA-2E-KE2-I/U-V3.0

Code: VBA-2E-KE2-I/U-V3.0

KE control cabinet module
2 analog inputs

Datasheet excerpt: Technical data of  VBA-2E-KE2-I/U-V3.0

Product Description
KE control cabinet module
2 analog inputs
General specifications
Node typeA/B node
AS-Interface specificationV3.0
Required gateway specification≥ V3.0
UL File NumberE223772
Indicators/operating means
LED FAULTerror display; LED red
red: communication error
red flashing: peripheral error or address 0
LED INTInternal input supply active; LED green
LED PWRAS-Interface voltage; LED green
green: AS-Interface voltage OK
green flashing: peripheral error or address 0
LED AUXext. auxiliary voltage UAUX ; LED green
LED -/OKStatus input signal; LED green
Off: Not connected (Only current module)
On: Signal within measuring range
Flashing: Signal outside measuring range
LED U/ICurrent or voltage module; Green LED
Off: Voltage input
On: Current input
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
(protection class 3 according to VDE 0106/IEC 364-4-41)
Insulation voltage≥ 500 V
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 80 mA
Input
Input voltageFor voltage module: ≤ 25 V per input
Number/Type2 analog inputs
Current: 4 ... 20 mA
voltage: 0 ... 10 V
Supplyfrom AS-Interface or from external auxiliary voltage as required UAUX
Input currentFor current module: ≤ 40 mA per input
Input resistanceFor current module: 50 Ω
For voltage module: 100 kΩ
Switching pointChangeover current/voltage module:
current module with Iin ≥ 1 mA
voltage module with Uin ≥ 1 V
Resolution14 Bit / 1 µA (Current module) or
14 bit / 1 mV (Voltage module)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 EN 61131-2:2007
Standard conformity
Degree of protectionEN 60529:2000
AS-InterfaceEN 62026-2:2013
Programming instructions
ProfileS-7.A.9
IO code7
ID codeA
ID2 code9
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.A.9.
Parameter bits (programmable via AS-i)function
P0mains power frequency filter
P0=1, 50 Hz filter active
P0=0, 60 Hz filter active
P1P1=1, normal operating mode
P1=0, both channels in current mode and without recognition of wire breakage
P2Message of peripheral error
P2=1, peripheral error is reported
P2=0, peripheral error is not reported
Ambient conditions
Ambient temperature0 ... 70 °C (32 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Connectionremovable terminals
rated connection capacity:
rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2
for multiple-wire connection with two wires of equal cross-section:
flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
Mass350 g
MountingDIN mounting rail

Classifications

SystemClasscode
ECLASS 13.027242601
ECLASS 12.027242601
ECLASS 11.027242601
ECLASS 10.0.127242601
ECLASS 9.027242601
ECLASS 8.027242601
ECLASS 5.127242601
ETIM 9.0EC001596
ETIM 8.0EC001596
ETIM 7.0EC001596
ETIM 6.0EC001596
ETIM 5.0EC001596
UNSPSC 12.139121535

Check out any spare parts and components from the Pepperl+Fuchs catalog!