AS-Interface safety module VBA-8E8A8A-KE4-ZEL/E2L/SEL
Brand: Pepperl+Fuchs
Code: VBA-8E8A8A-KE4-ZEL/E2L/SEL
KE4 switch cabinet module
8 safety-related electronic outputs, each switchable with a standard output, 8 standard inputs
Datasheet excerpt: Technical data of VBA-8E8A8A-KE4-ZEL/E2L/SEL
Product Description |
---|
KE4 switch cabinet module 8 safety-related electronic outputs, each switchable with a standard output, 8 standard inputs |
General specifications | ||
---|---|---|
Node type | A/B slave, 2 standard slaves for inputs/outputs, additional slaves can be configured | |
AS-Interface specification | V3.0 | |
Required master specification | ≥ V3.0 | |
Indicators/operating means | ||
LED FAULT | error display; LED red red: communication error | |
LED AS-i | AS-Interface voltage; LED green | |
LED AUX | ext. auxiliary voltage UAUX ; LED green | |
LED IN | switching state (input); 8 LED yellow | |
LED OUT | Switching state (output); 8 LED yellow | |
LED ALARM | Alarm signal from the control; yellow LED | |
Electrical specifications | ||
Auxiliary voltage (input) | 24 V (20 VDC ... 30 VDC) PELV Max. current consumption: 8 A | |
Rated operating voltage | 18,0 ... 31.6 V from AS-Interface | |
Rated operating current | < 200 mA | |
Interface 1 | ||
Interface type | Chip card slot | |
Input | ||
Number/Type | 8 digital inputs | |
Supply | from external auxiliary voltage UAUX | |
Voltage | 24 V DC | |
Switching threshold | U < 5 V (low) U > 15 V (high) | |
Output | ||
Number/Type | 8 safe electronic outputs 1 - 8 release circuits | |
Supply | from external auxiliary voltage UAUX | |
Current loading capacity | 2 A per output, 8 A total Note derating | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Machinery Directive | ||
Directive 2006/42/EC | EN 13849-1:2008/AC:2009 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Electrical safety | EN 13849-1:2008/AC:2009 | |
Climatic conditions | EN 61131-2:2007 | |
AS-Interface | EN 62026-2:2013 | |
Functional safety | EN 61508:2010 EN 62061:2005/A1:2013 | |
Programming instructions | ||
Profile | Diagnostic slave: S-7.A.E, ID1 = 5 Input/output slave: S-7.F.E, ID1 = F Configuration slave: S-7.A.5, ID1 = 7 | |
Ambient conditions | ||
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Altitude | 0 ... 2000 m | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2 | |
Material | ||
Housing | PA 66-FR | |
Mass | 270 g | |
Mounting | DIN mounting rail |
Classifications
System | Classcode |
---|---|
ECLASS 13.0 | 27272603 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
Check out any spare parts and components from the Pepperl+Fuchs catalog!
Do you want to order a AS-Interface safety module VBA-8E8A8A-KE4-ZEL/E2L/SEL with code: VBA-8E8A8A-KE4-ZEL/E2L/SEL?
Leave your request on our website for immediate assistance!